| KDJB-802 Microcomputer Relay protection Tester |
| AC Current Output |
|
| Phase Current Output (RMS) |
0-40A per phase |
| Three-way Parallel Current Output (RMS) |
0-120A |
| Permitted Long-Term Phase Current (RMS) |
10A per phase |
| Maximum Phase Current Output Capacity |
450VA |
| Maximum Capacity at 120A Three-way Parallel Current |
1200VA |
| Permitted Operating Time at 120A Three-way Parallel Current |
8s |
| Frequency Range (Fundamental) |
20-1000Hz |
| Harmonic Order |
1-9 |
| DC Current Output |
|
| Phase Current Output |
0-±20A per phase |
| Maximum Output Load Voltage |
20V |
| AC Voltage Output |
|
| Phase Voltage Output (RMS) |
0-130V |
| Line Voltage Output (RMS) |
0-260V |
| Phase Voltage / Line voltage output power |
80VA/160VA |
| Frequency Range (Fundamental) |
20-1000Hz |
| Harmonic Order |
1-9 |
| DC Voltage Output |
|
| Phase Voltage Output Amplitude |
0-±180V |
| Line Voltage Output Amplitude |
0-±360V |
| Phase Voltage/Line Voltage Output Power |
80VA/160VA |
| Switch Inputs |
|
| Open Contact |
1-20mA, 24V |
| Position Contact Input |
"0": 0-+6V; "1": +11V-+250V |
| Switch Output |
|
| Open Contact |
DC: 220V/0.2A; AC: 220V/0.5A |
| Time Measurement Range |
0.1ms-9999s |
| Power Supply Voltage Range |
AC 220V±10%, 50/60Hz |
| Ambient Temperature Range |
-10°C-+50°C |
| Dimensions |
450×360×235mm³ |
| Weight |
15kg |
| Accuracy within rated current range |
|
| AC phase current |
<0.2% ±0.1% FS (FS is full scale) |
| AC high current terminal output |
<0.2% ±0.1% FS |
| DC current |
<0.5% ±0.1% FS |
| Accuracy within rated voltage range |
|
| AC voltage |
<0.2% ±0.1% FS (FS is full scale) |
| DC voltage |
<0.5% ±0.1% FS |
| Accuracy within other rated ranges |
|
| Frequency accuracy (at 50 Hz) |
<0.001 Hz ±0.1% FS (FS is full scale) |
| Phase accuracy |
<0.5° |
| Harmonic distortion |
<0.5% |
| Time measurement accuracy |
<0.1ms |