Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. Accuracy
|
Cx ± (reading × 1%+1pF)
|
Tg δ ± (reading × 1%+0.00040)
|
|
2. Anti interference index
|
frequency conversion anti-interference, can still achieve the above accuracy under 200% interference
|
3. Capacitance range
|
internal applied high voltage 3pf ~ 60000pf / 10kV
|
60pF1 μ F/0.5kV
|
|
External applied high pressure
|
3pf 1.5 μ F/10kV
|
60pF30 μ F/0.5kV
|
|
4. Resolution
|
up to 0.001pf, 4 significant digits
|
5. CVT transformation ratio measurement
|
transformation ratio of 35-500kV CVT device
|
Measuring range of transformation ratio
|
10 ~ 99999
|
Transformation ratio measurement accuracy
|
± reading X1%
|
Phase measurement range
|
0 ~ 359.999 °
|
Phase measurement accuracy
|
± 0.002 °
|
6. CVT self excitation method
|
low voltage output output voltage 3 ~ 50V
|
Output current
|
3 ~ 30A
|
7tg δ Range
|
unlimited, automatic identification of capacitance, inductance and resistance
|
Resolution
|
0.00001
|
8. Test current range
|
10 μ A5A
|
9. Internal high voltage
|
set voltage range 0.5 10KV
|
Maximum output current
|
200mA
|
Pressure rise and fall mode
|
continuous and smooth adjustment
|
Voltage accuracy
|
± (1.5%) × Reading + 10V)
|
Voltage resolution
|
1V
|
10. Externally applied high voltage
|
maximum test current 1A when positive connection
|
Power frequency or frequency conversion
|
40 ~ 70Hz
|
Maximum test current during reverse wiring
|
1A / 10kV
|
Power frequency or frequency conversion
|
40 ~ 70Hz
|
11. Test frequency
|
45Hz, 50Hz, 55Hz, 60Hz, 65Hz single frequency
|
45 / 55Hz, 55 / 65Hz, 47.5/52.5hz automatic double frequency conversion
|
|
Frequency accuracy
|
± 0.01Hz
|
12. Measurement time
|
About 40s, related to measurement method
|
13. Input power supply
|
180V ~ 270vac, 50Hz / 60Hz ± 1%, mains or generator power supply
|
14. Ambient humidity
|
- 10 ~ 50
|
15. Relative humidity
|
< 90%
|