| AC Hipot Test | |
| Rated Output Capacity |
200VA, short-circuit current greater than 200mA
|
| AC Voltage Output |
Range: (50 ~ 5000)V, resolution: 1V, error: ±(1.5% × set value + 5V)
|
| AC Voltage Measurement |
Range: (0.050 ~ 5.000)kV, resolution: 0.001kV, error: ±(1.5% × reading + 5 digits)
|
| Current Measurement Accuracy |
Range: 0.010~3.500mA, 3.00~40.00mA, Resolution: 0.001/0.01mA, Error: ±(1.5% × Reading + 5 digits)
|
| Output Frequency | 50Hz/60Hz, Accuracy: ±0.1Hz |
| Output Regulation | ±(1.5% × Set Value + 5V), no-load to full-load |
| Waveform Distortion | Sine wave, <1.5% (resistive load) |
| Ramp-Up/Ramp-Down Time |
Range: 0, (0.1~999.9)s, Resolution: 0.1s
|
| Test Time |
Range: 0, (0.5 to 999.9) s, Resolution: 0.1 s, Accuracy: ±(1% × set value + 1 digit)
|
| Arc detection |
1~9 (9 is most sensitive), 0 disables arc function
|
| Current compensation |
0.000~40.00 mA, total current + compensation current < 40 mA, automatic
|
| DC Hipot Test | |
| DC Voltage Output |
Range: (50~6000)V DC, Resolution: 1V, Error: ±(1.5% x set value + 5V)
|
| DC Voltage Measurement |
Range: (0.050~6.000)kV DC, Resolution: 1V, Error: ±1.5% x reading + 5 digits
|
| Output Ripple |
<2% (6kV/1mA resistive load)
|
| Output Regulation |
±(1.5% x set value + 2V), no-load to full-load
|
| DC Current Measurement |
Range: 0.0~350.0μA/300~3500μA/3.00~10.00mA, Resolution: 0.1μA/1μA/0.01mA, Error: ±(1.5% x reading + 5 digits)
|
| Ramp-up time |
Range: 0, (0.4-999.9)s, 0 = off
|
| Test time |
Range: 0, (0.5-999.9)s, 0 = infinite, Resolution: 0.1s, Error: ± 1% x set value + 1 digit
|
| Ramp-Down Time | Range: 0, (1.0 ~ 999.9) s, 0 = Off |
| Arc Detection | 1 ~ 9 (9 is most sensitive), 0 = Arc Off |
| Current Compensation |
(0-2000.0)μA, Automatic
|
| Discharge Time |
≤ 400 ms
|
| Maximum Capacitive Load | 1uF < 1kV, 0.75uF < 2kV, 0.5uF < 3kV, 0.08uF < 4kV, 0.04uF < 5kV |
| Insulation Resistance Tester | |
| DC Voltage Output |
Range: (50~6000)V DC, Resolution: 1V, Error: ±(1.5% x set value + 5V)
|
| DC Voltage Measurement |
Range: (0.050~6.000)kV DC, Resolution: 1V, Error: ±1.5% x reading + 5 digits
|
| Resistance Upper and Lower Limits |
Range: 0.10 MΩ ~ 50,000.00 MΩ, including the upper limit setting
|
| Insulation Resistance Measurement |
Range: 0.100 MΩ ~ 50.00 GΩ, Resolution: 0.001 MΩ / 0.01 MΩ / 0.1 MΩ / 0.001 GΩ / 0.01 GΩ
Error: 100 V ~ 499 V: 0.100 MΩ ~2.000 GΩ, ±(5% × reading + 2 digits)
500 V ~ 6000 V: 1.000MΩ ~ 999.9MΩ: ±(2% × reading + 2 digits)
1.000GΩ ~ 9.999GΩ: ±(5% × reading + 2 digits)
10.00GΩ ~ 50.00GΩ: ±(15% × reading + 2 digits)
|
| Ramp-up time |
Range: 0, (0.1-999.9)s, 0 = off
|
| Test time |
Range: 0, (0.5-999.9)s, 0 = infinite, Resolution: 0.1s, Error: ± 1% x set value + 1 digit
|
| Ramp-Down Time | Range: 0, (1.0 ~ 999.9) s, 0 = Off |
| Arc Detection | 1 ~ 9 (9 is most sensitive), 0 = Arc Off |
| Current Compensation |
(0-2000.0)μA, Automatic
|
| Discharge Time |
≤ 400 ms
|
| Maximum Capacitive Load | 1uF < 1kV, 0.75uF < 2kV, 0.5uF < 3kV, 0.08uF < 4kV, 0.04uF < 5kV |
| Ground Resistance Test | |
| Rated Test |
Maximum Current 32A, Maximum Resistance 600mΩ, Open-Circuit Voltage Less Than 12V
|
| Output Current |
Range: (2.0A - 32.0A) AC, Resolution: 0.1A, Accuracy: ±(1.5% × set value + 2 digits)
|
| Current Fluctuation |
≤0.4% × set value/minute
|
| Output Voltage |
Range: (3.0V - 6.4V) AC, Resolution: 0.1V, Accuracy: ±(1.5% × reading + 2 digits) in open-circuit conditions
|
| Output Frequency |
50Hz / 60Hz, Accuracy: ±0.1Hz
|
| Resistance Measurement |
Range: (10.0 - 99.9)mΩ, (100 - 600)mΩ, Resolution: 0.1/1 mΩ;
Measurement Error: <100 mΩ, ±(1.5% × reading + 1 mΩ); ≥100 mΩ, ±(2% × reading + 2 digits)
|
| Resistance Compensation | (0-200) mΩ |
| Test Time | Range: 0, (0.5-999.9) s, 0 = infinite; Resolution: 0.1 s; Error: ±1% × set value + 1 digit |
| System General Specifications | ||
| Installation Location | Indoors, altitude not exceeding 2000m | |
| Operating Environment |
Temperature | 0-40°C |
| Humidity | 40°C, (20-90)%RH | |
| Storage Environment |
Temperature | -10-50°C |
| Humidity | 50°C, 90%RH, 24h | |
| Input Power | AC, 220V+10%, 50Hz+5%, 10A | |
| Power Consumption |
No-load | <20W |
| Full-load | <80W | |
| Dimensions (mm) | 215(W) x 88(H) x 315(D) | |
| Weight | Approximately 5.3kg | |