KDJB-1200Y Microcomputer Relay protection Tester |
Current Channels |
Standard 6-Phase |
Voltage Channels |
Standard 6-Phase |
AC Current Output Range |
30A/Phase or 180A (6-Phase Parallel) |
DC Current Output Range |
10A/Phase |
AC Voltage Output Range |
120VAC/Phase |
DC Voltage Output Range |
160VDC/Phase |
AC Current Output |
|
6-Phase Current Output (RMS) |
0-30A per phase, output accuracy: 0.2 level |
3-Phase Current Output (RMS) |
0-60A per phase |
6-Phase Parallel Current Output (RMS) |
0-180A |
Permitted Long-Term Phase Current Operating Range (RMS) |
10A |
Maximum Phase Current Output Power |
300VA |
Maximum Output Power at Maximum 6-Phase Parallel Current Output |
1000VA |
Permitted Operating Time at Maximum 6-Phase Parallel Current Output |
10s |
Frequency Range (Fundamental) |
1-1000Hz |
Harmonic Order |
1-20 |
DC Current Output |
|
Current Output |
0-±10A per phase, output accuracy: 0.5 level |
Maximum Output Load Voltage |
20V |
AC Voltage Output |
|
Phase Voltage Output (RMS) |
0-120V, output accuracy: 0.2 level |
Line Voltage Output (RMS) |
0-240V |
Phase Voltage / Line voltage output power |
80VA/100VA |
Frequency range (fundamental) |
1-1000Hz |
Harmonic order |
1-20 |
DC voltage output |
|
Phase voltage output amplitude |
0-±160V, output accuracy: 0.5 |
Phase voltage output amplitude |
0-±320V |
Phase voltage/line voltage output power |
70VA/140VA |
Switch inputs |
|
10 switch inputs |
open contact, 1-20mA, 24V;
potential contact input, "0": 0-+6V; "1": +11V-+250V
|
8 pairs of switch outputs |
DC: 220V/0.2A; AC: 220V/0.5A |
Time measurement range |
0.1ms-9999s, measurement accuracy: <0.1ms |
Dimensions |
360×350×180mm |
Unit weight |
17kg |