AC current output
Output accuracy: 0.2 level Phase current output (effective value): 0-40A Triple current output (effective value): 0-120A Long term allowable operating value (effective value) of phase current: 10A Maximum output power of phase current: 420VA Maximum output power at maximum output of triple current: 900VA Allowable working time for maximum output of triple current: 10s Frequency range (fundamental): 20-1000Hz Harmonic frequency: 1-20 times DC current output
Output accuracy: 0.2 level Current output: 0~± 10A per phase, 0~± 30A per triple junction Maximum output load voltage: 20V AC voltage output
Output accuracy: 0.2 level Phase voltage output (effective value): 0-120V Line voltage output (effective value): 0-240V Phase voltage/line voltage output power: 80VA/100VA Frequency range (fundamental): 20-1000Hz Harmonic frequency: 1-20 times DC voltage output Output accuracy: 0.2 level Phase voltage output amplitude: 0 to ± 160V Line voltage output amplitude: 0 to ± 320V Phase voltage/line voltage output power: 70VA/140VA Measurement of switch quantity and time
Switch input: industrial control type, 10 channels; Empty contact: 1-20mA, 24V; Potential contact connection: "0": 0~+6V; "1":+11 V~ +250V Switching output: industrial control type, 8 pairs; DC:220V/0.2A;AC:220V/0.5A; Time measurement: measurement range of 0.1ms to 9999s; Measurement accuracy of 0.1ms;