Customization: | Available |
---|---|
Warranty: | 1 Year |
Relative Humidity: | ≤ 80% |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. Operating environment
|
|
(1) Ambient temperature
|
- 10 ºC~ 40 ºC
|
(2) Relative humidity
|
≤ 80%
|
2. Measurement accuracy
|
|
The measuring accuracy of this instrument is Level 1.
|
|
Ratio difference
|
Δ f =±(1% × f+1% ×δ) ±0.01(%)
|
Angle difference
|
Δδ= ±(1% ×δ+ 1% × f) ± 1 (min)
|
Conductivity value
|
G=± (1% × G+1% ×δ ±0.01) mS
|
Electrical susceptance
|
δ= ± (1% ×δ+ 1% × G±0.01)mS
|
Load
|
S=± (1% × S±0.1)VA
|
Resistance
|
R=± (1% × R+1% × X±0.1)Ω
|
Reactance
|
X=± (1% × X+1% × R±0.1)Ω
|
3. Charging power supply
|
AC 176V~264V, frequency 45-55Hz
|
4. Insulation
|
|
(1) . The insulation resistance of the voltage and current input terminals to the enclosure is ≥ 100MΩ.
|
|
(2) The working power supply input end bears power frequency 2kV (effective value) between the shell, and the test lasts for 1minute.
|
|
5. Battery working time
|
more than 6 hours after full charge.
|
6. Volume
|
|
Host
|
32cm × 24cm × 13cm
|
Extension
|
32cm × 24cm × 13cm
|
7. Weight
|
|
Host
|
2.5Kg
|
Extension
|
2Kg
|