Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 Year |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input power
|
three phase AC380V ± 10%, 50Hz
|
||
output
|
AC 200V accuracy: 1%
|
||
Maximum current
|
|||
Output
|
5A
|
||
Maximum current
|
|||
signal frequency
|
42.5Hz/57.5Hz;45Hz/55Hz;47.5Hz/52.5Hz;50Hz/50Hz
|
||
Measurement range
|
positive sequence capacitance
|
positive sequence impedance
|
impedance angle
|
Zero sequence capacitance
|
Zero sequence impedance
|
||
Coupling capacitance
|
Mutual inductance reactance
|
||
0.1~50μF
|
0.5~400Ω
|
0~360°
|
|
Measurement resolution
|
0.01μF
|
0.01Ω
|
0.01°
|
Measurement accuracy
|
0.1μF~1μF
|
0.5Ω~1Ω
|
±0.2°(voltage>1.0V)
|
±3%±0.05μF
|
±3%±0.05Ω
|
±0.3°(voltage>0.2~1.0V)
|
|
1μF~50μF
|
01Ω~400Ω
|
|
|
±1.5%±0.03μF
|
±3%±0.03Ω
|
|
|
Overall dimension
|
620 mm × 500 mm × 600mm (including wheels); Weight: 79kg
|
||
Operating environment ambient temperature
|
Ambient temperature: - 15 ºC ~ + 40 ºC relative humidity: < 90%
|
||
Anti interference parameters
|
Interference voltage: the longitudinal induced voltage after connecting the instrument test power supply is less than 350V;
|
||
Interference current: < 40A when both ends of the line are short circuited and grounded;
|
|||
It can stably and accurately complete the test under the condition that the ratio of the output signal of the instrument to the
interference signal is 1:10. |