1. Sampling methods: Low voltage pulse method, impulse flashover method, triple pulse method, multiple pulse method, velocity measurement method
2. Sampling rates: 200 MHz, 100 MHz, 80 MHz, 40 MHz, 20 MHz, 10 MHz
3. Pulse width: 0.05 μ s. 0.1 μ s. 0.2 μ s. 0.5 μ s. 1 μ s. 2 μ s. 8 μ S
4. Wave speed setting: cross-linked ethylene, polyvinyl chloride, oil immersed paper, non dripping oil, and unknown type self setting
5. Impulse high voltage: 35kV and below
6. Applicable cable voltage: 380V, 600V, 10kV, 35kV, 110kV, 220kV
7. Testing distance: < 60km
8. Blind spot: ≤ 0.5m
9. Resolution: 0.5m
10. Testing accuracy: 0.5m
11. Impulse high voltage: optional for 0-8kV, 0-16kV, and 0-32kV
12. High voltage division: voltage accuracy level 1.5
13. Built in capacitor: 8 μ F/32kV, 8 μ F/16kV, 2 μ F/32kV
14. First gear 0-8000V: The capacitance value is 32 µ F;
15. Second gear 0-16000V: The capacitance value is 8 µ F;
16. Third gear 0-32000V: The capacitance value is 2 µ F
17. Adjustable discharge cycle: The discharge cycle can be adjusted from 0 to 99 seconds
18. Adjustable discharge time: The discharge time can be adjusted from 1 to 99 seconds, usually set at 0.3 seconds
19. High voltage output mode: DC, single pulse, periodic pulse
20. Maximum energy storage: ≥ 1024J
21. Impact time: Automatic impact for about 4 seconds, manual impact can control the time
22. Impulse power: 2kVA
23. Working power supply: AC 220V ± 10% 50Hz ± 2Hz
24. Working temperature: -10 ºC~40 ºC
25. Working humidity: ≤ 80%
26. Altitude: ≤ 1000 meters